Di-LOG

Apollo 600 Elite Bundle

Apollo 600 Elite Bundle

Apollo 600 Elite Bundle

Seaward Apollo 600 Elite PAT Tester Bundle

PATSolutions is a way of approaching all aspects of electrical testing. From the testers themselves to information management software, through to labels, printers and more. The Apollo 600 Elite Bundle has everything you’ll need.

You can buy each tester and its accessories separately or as an optional PATSolutions package which includes everything you need to run an efficient, effective PAT Testing business.

The Apollo 600 Pro Kit package includes:
1. Seaward Apollo 600

The PrimeTest 350 is derived from the PrimeTest 300 but has the following extra features:

  • The batteries are charged while they’re in the unit, via a charging port. Charging time is four hours.
  • USB download for transferring data to a PC.
  • Alternative leakage test, as described in the IET Code of Practice.
  • 250V Insulation Test. For use when suppressors or other components prevent a 500V Insulation test.
  • Load measurement. During the protective conductor and touch current tests, the load is measured and displayed as both a power and current measurement.

2. Test n Tag Elite Printer

A handy, hard wearing printer, with Impact-modified polycarbonate with fused oil and abrasion resistant rubber overmould (six foot drop protection). Featuring smart battery management to, monitor the battery for longer life and performance. Labels are tamperproof, waterproof and professionally printed with your logo and barcode, and less than 3p a label! Compatible with PrimeTest 350 and PrimeTest 300.

3. Bluetooth Laser Scanner

A portable ID laser scanner with Bluetooth interface. Extremely compact and lightweight, making it ideal for mobile applications. Powered by standard LR-3 (AAA) batteries.

4. PAT Checkbox

Designed to provide a safe, simple and quick way to check a PAT Tester’s calibration. Checkbox can even check Portable Appliance Testers outside the Seaward range.

PATGuard Elite 3 Software (Subscription required)

If you PAT Test on a regular basis this is an ideal bit of software. It gives you complete quick and easy management of the PAT Testing process. One program supplies the total solution. From the first test, to downloading results, certificates, planning re-tests and uploading.

A must for any PAT Tester.

  • Calibration Certificate
  • PATGuard Support Contract
  • Battery Charger
  • Connectors
  • Carrying Case

Click here to request more info or arrange a demonstration

Di-LOG is a part of the Di-LOG group, for more information click the link to view our group divisions.

ApolloFront_000

 

ApolloshowingCamera

 

BluetoothbarcodeScanner

 

TestnTagElite

Specifications

Earth Continuity
Test Current± 200mA
Display Range0.01 Ω – 19.99Ω
Pass ValueUser Defined
Insulation Resistance
Test Voltage500V / 250V DC @ 1mA nominal
Display Range0.01MΩ - 19.99MΩ
Pass ValueUser Defined
IEC Lead Test
Tests PerformedEarth, Insulation Resistance, Live & Neutral Continuity
Protective Conductor Current/Load
Test Voltage195V - 230V, 45Hz-60Hz
Display Ranges0.15mA – 19.99mA
0.00kVA – 4.00kVA
0.00A – 16.00A
Pass ValueUser Defined
Protective Conductor Current/Load
Test Voltage195V - 230V, 45Hz-60Hz
Display Ranges0.07mA – 3.5mA
0.00kVA – 4.00kVA
0.00A – 16.00A
Pass ValueUser Defined
Alternative Leakage Current
Test Voltage40V, 50Hz
Display Range0.10mA - 19.99mA
Pass ValueUser Defined
RCD Trip Time
Test Current30mA rms, 0º/180º auto switched
Display Range0ms - 200ms
Loop Impedance
Test CurrentNon-tripping for >30mA RCD
Display Range0.0Ω - 199Ω
Power Socket Test
Display Range0ms - 2000ms
Test MethodInternal isolation to avoid tripping distribution board RCD
Power Socket Test
Voltage Range195V – 253V
Voltage Indicatorsphase–Earth & phase–neutral
General
Memory size8000 records
Weight0.9kg
Dimensions260mm x 100mm x 55mm
Power Source6 x AA NiMH rechargeable batteries